13 :

External Base Block by N.C. Contact

Base block operation is the same as described above, except that the Base Block contact must be

open

to be recognized.

D.

Data

14

: Speed Search From Max Frequency

Data

15

: Speed Search From Set Frequency

A multi-function input terminal is utilized to activate speed search. When the external speed search
command is closed, the base is blocked for the min. base block time, then the speed search is
made. The operation depends on the set value.

IMPORTANT

Set values

14

and

15

CANNOT be selected in combination.

• When

14

is set, the speed search begins with the maximum frequency.

• When

15

is set, the speed search begins with the frequency command

command that has been set after the search command was received.

RUN

SIGNAL

SPEED SEARCH

MAX FREQ., OR FREQ.

REF. WHEN SPEED

SEARCH IS INPUTTED

OUTPUT FREQUENCY

VOLTAGE AT

SPEED SEARCH

OUTPUT VOLTAGE

MIN.

BASE

BLOCK

TIME

SPEED SEARCH

OPERATION

WITHIN 0.5 SEC

NOTE: When continuous operation mode at momentary stop function is selected,

the Speed Search command must be enabled.

Speed Search Operation Timing

SPEED COINCIDENCE
POINT

RETURN TO
NORMAL V/f
OUTPUT

5.17 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S5)