beautypg.com

3 status indicator leds, 4 monitor displays, Status indicator leds -3 – Yaskawa J7 Drive User Manual

Page 34: Monitor displays -3

background image

4-3

There are two indicator LEDs on the front of the Drive. The Drive status is indicated by various
combinations of ON, Blinking, and OFF conditions of these two LEDs:

For details of how the status indicator LEDs function during a drive fault, refer to the
“TROUBLESHOOTING” section.

4.3 STATUS INDICATOR LEDs

When using the

Monitor

Function, a variety of information will appear on the Digital Operator

display when each of the U-XX (display only) parameters is selected.

CONSTANT

DISPLAY

Un-

MONITORED ITEM

EXAMPLE

01

Frequency reference (Hz)

60.0

02

Output frequency (Hz)

60.0

03

Output current (A)

12.5

04

AC output voltage (V)

230

05

DC Bus voltage (VPN)

325

06

Input terminal status

II

I

I

I

I (1)

07

Output terminal status

IIIII

I

(2)

09

Fault record (last record faults)

(3)

oC

10

Software number

013

XXX

15

Data reception error

0

PARAMETER

DISPLAY

U -

MONITORED ITEM

EXAMPLE

4.4 MONITOR DISPLAYS

(1)

Actual display appearance:

(2)

Actual display appearance:

(3)

See section 6 for viewing

of fault log contents.

Term. S5 input OPEN

Not used

Term. S1 input OPEN

Term. S2 input CLOSED

Term. S3 input OPEN

Term. S4 input CLOSED

MA-MC CLOSED

Not used

{

(Green)

(Red)

CONDITION

RUN

ALARM

Operation Ready (during stop)

Blinking

Off

Ramp to Stop (during decel)

Long Blinking

Off

Normal Operation (running)

On

Off

Alarm

Blinking or ON

Blinking

Fault

Off

On