3 status indicator leds, 4 monitor displays, Status indicator leds -3 – Yaskawa J7 Drive User Manual
Page 34: Monitor displays -3

4-3
There are two indicator LEDs on the front of the Drive. The Drive status is indicated by various
combinations of ON, Blinking, and OFF conditions of these two LEDs:
For details of how the status indicator LEDs function during a drive fault, refer to the
“TROUBLESHOOTING” section.
4.3 STATUS INDICATOR LEDs
When using the
Monitor
Function, a variety of information will appear on the Digital Operator
display when each of the U-XX (display only) parameters is selected.
CONSTANT
DISPLAY
Un-
MONITORED ITEM
EXAMPLE
01
Frequency reference (Hz)
60.0
02
Output frequency (Hz)
60.0
03
Output current (A)
12.5
04
AC output voltage (V)
230
05
DC Bus voltage (VPN)
325
06
Input terminal status
II
I
I
I
I (1)
07
Output terminal status
IIIII
I
(2)
09
Fault record (last record faults)
(3)
oC
10
Software number
013
XXX
15
Data reception error
0
PARAMETER
DISPLAY
U -
MONITORED ITEM
EXAMPLE
4.4 MONITOR DISPLAYS
(1)
Actual display appearance:
(2)
Actual display appearance:
(3)
See section 6 for viewing
of fault log contents.
Term. S5 input OPEN
Not used
Term. S1 input OPEN
Term. S2 input CLOSED
Term. S3 input OPEN
Term. S4 input CLOSED
MA-MC CLOSED
Not used
{
(Green)
(Red)
CONDITION
RUN
ALARM
Operation Ready (during stop)
Blinking
Off
Ramp to Stop (during decel)
Long Blinking
Off
Normal Operation (running)
On
Off
Alarm
Blinking or ON
Blinking
Fault
Off
On