A.

n49 :

Prohibited Frequency 1

Factory setting (each):

0.0

n50 :

Prohibited Frequency 2

Range (each): 0.0 to 400 Hz

These parameters allow programming of up to three prohibited frequency points for eliminating
problems with resonant vibration of the motor/machine. This feature does not actually eliminate the
selected frequency values, but will accelerate and decelerate the motor through the prohibited
bandwidth.

B.

n51 :

Prohibited Frequency Deadband

Factory setting:

0.0

Range: 0.0 to 25.5 Hz

This parameter determines the width of the deadband around each selected prohibited frequency
point. The factory setting is " 1.0 ", which establishes a deadband of ±1.0 Hz.

EXAMPLE:

Vibration encountered between 30.0 and 36.0 Hz.
SOLUTION:

Set

n49

to " 33.0 ". This is the center of the problem

frequency band.

Set

n51

to " 3.0 ". This will cause the Drive to reject all

frequency command values between 30.0 and 36.0 Hz.

A frequency command in the deadband will be converted to the bottom
value of the deadband, e.g. a command of 33 Hz would result in a run
frequency of 30 Hz.

NOTE:

n49

>

n50

- The highest prohibit frequency required needs to be in

n49

and the

lowest prohibit frequency needs to be in

n50

.

FREQ. CMD

36 Hz

n49

= 33 Hz

30 Hz

0

Total Deadband = 6.0 Hz

±

n51

(3.0 Hz)

OUTPUT FREQUENCY (Hz)

5.6 CRITICAL FREQUENCY REJECTION