Current ratings & horsepower range, Warning – Yaskawa J7 Drive User Manual
Page 3

- i -
CURRENT RATINGS & HORSEPOWER RANGE
RATED
CURRENT
NOMINAL
OLD DRIVE
NEW DRIVE
INPUT
RATING (AMPS)
HORSEPOWER
MODEL NO.
MODEL NO.
CIMR-J7AM
0.8
1/8
JDA001
20P10
1.6
1/4
JDA002
20P20
2
3.0
1/2
JDA003
20P40
3
5.0
3/4 & 1
JDA005
20P70
0
8.0
2
JDA008
21P50
V
11.0
3
JDA011
22P20
17.5
5
JDA017
23P70
1.2
1/2
JDB001
40P20
4
1.8
3/4
JDB002
40P40
6
3.4
1 & 2
JDB003
40P70
0
4.8
3
JDB005
41P50
V
5.5
3
–
42P20
7.2
3
–
43P00
8.6
5
JDB009
43P70
WARNING
Do not touch circuit components until main input power has been turned OFF.
Status indicator LEDs and Digital Operator display will be extinguished when
the DC bus voltage is below 50 VDC. Wait at least one additional minute.
Do not connect or disconnect wires and connectors while the main input
power is turned on.
CAUTION
The drive leaves the factory with parameters initialized for 2-Wire control
(when using external Run/Stop signals). Before using the initialization
function of constant n01 , know your control wiring configuration:
10 = Factory 2-Wire Control Initialization (Maintained RUN Contact)
11 = Factory 3-Wire Control Initialization (Momentary START/STOP Contact)
Entering either Initialization code resets all parameters to factory settings, and
automatically returns parameter n001 setting to “ 1 ”. If the drive is
connected for 3-Wire control and this parameter is set to “ 10 ” (2-Wire Control
Initialization), the motor may run in reverse direction WITHOUT A RUN
COMMAND APPLIED. Equipment damage or personal injury may result.