- i -

CURRENT RATINGS & HORSEPOWER RANGE

RATED

CURRENT

NOMINAL

OLD DRIVE

NEW DRIVE

INPUT

RATING (AMPS)

HORSEPOWER

MODEL NO.

MODEL NO.

CIMR-J7AM

0.8

1/8

JDA001

20P10

1.6

1/4

JDA002

20P20

2

3.0

1/2

JDA003

20P40

3

5.0

3/4 & 1

JDA005

20P70

0

8.0

2

JDA008

21P50

V

11.0

3

JDA011

22P20

17.5

5

JDA017

23P70

1.2

1/2

JDB001

40P20

4

1.8

3/4

JDB002

40P40

6

3.4

1 & 2

JDB003

40P70

0

4.8

3

JDB005

41P50

V

5.5

3

42P20

7.2

3

43P00

8.6

5

JDB009

43P70

WARNING

Do not touch circuit components until main input power has been turned OFF.
Status indicator LEDs and Digital Operator display will be extinguished when
the DC bus voltage is below 50 VDC. Wait at least one additional minute.

Do not connect or disconnect wires and connectors while the main input
power is turned on.

CAUTION

The drive leaves the factory with parameters initialized for 2-Wire control
(when using external Run/Stop signals). Before using the initialization
function of constant n01 , know your control wiring configuration:

10 = Factory 2-Wire Control Initialization (Maintained RUN Contact)
11 = Factory 3-Wire Control Initialization (Momentary START/STOP Contact)

Entering either Initialization code resets all parameters to factory settings, and
automatically returns parameter n001 setting to “ 1 ”. If the drive is
connected for 3-Wire control and this parameter is set to “ 10 ” (2-Wire Control
Initialization), the motor may run in reverse direction WITHOUT A RUN
COMMAND APPLIED. Equipment damage or personal injury may result.