Yaskawa J7 Drive User Manual
Page 56
5-21
Continued
5.17 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S5)
DATA
FUNCTION
DESCRIPTION*
FWD/REV selection (for
MUST BE SET ONLY IN
n37
. Redefines terminals:
0
3-wire control)
S1 = Run; S2 = Stop;
S3 = FWD/REV select
2
Reverse Run/Stop command
Closed = Run Reverse (2-wire control)
(for 2-wire control)
Open = Stop
Drive trips; Digital Operator displays "
EFX
",
3
External fault (N.O. contact input)
where X is 2-5, corresponding to the terminal,
4
External fault (N.C. contact input)
S2-S5, which is receiving the fault input signal
5
Fault Reset
Resets fault, only if RUN command is not present
6
Multi-step frequency ref. select A
7
Multi-step frequency ref. select B
See paragraph 5.11B
8
Multi-step frequency ref. select C
10
Jog selection
Closed = Jog selected
See paragraph 5.12
11
Accel/decel time selection
Open = Accel/decel by
n16
/
n17
Closed = Accel/decel by
n18
/
n19
See paragraph 5.2
12
External base block
Closed = Shuts off Drive output
(N.O. contact input)
(frequency command is held)
13
External base block
See paragraphs 5.17B, 5.17C
(N.C. contact input)
14
Speed Search 1
Closed * = Speed Search operation from
maximum frequency
See paragraph 5.17D
15
Speed Search 2
Closed * = Speed Search operation from set frequency
See paragraph 5.17D
16
Accel/Decel Hold
See paragraph 5.17F
17
Remote/Local selection
See paragraph 5.17A
Drive operation & reference/
Open = Operates according to setting of
n003
&
n004
18
serial communication selection
Closed = Operates from serial communication
See paragraph 5.13
Fast Stop - Fault
Open = No effect
19
(Normally Open Contact)
Closed = If
n04
= 0, ramp to stop using
n19
Closed =
If
n04
= 1, coast to stop
Fast Stop - Alarm
Open = No effect
20
(Normally Open Contact)
Closed = If
n04
= 0, ramp to stop using
n19
Closed =
If
n04
= 1, coast to stop
Fast Stop - Fault
Open = If
n04
= 0, ramp to stop using
n19
21
(Normally Closed Contact)
Open =
If
n04
= 1, coast to stop
Closed = No effect
Fast Stop - Alarm
Open = If
n04
= 0, ramp to stop using
n19
22
(Normally Closed Contact)
Open =
If
n04
= 1, coast to stop
Closed = No effect
34
Up/Down function
See paragraph 5.17E
(can only be set in
n39
)
35
Loop Test (Serial Communications)
See paragraph 5.14D
Can only be set in n39
Table 5-2. n36 thru n39 Data Settings
* All contact closures must be maintained, except for speed search, which may