beautypg.com

Yaskawa J7 Drive User Manual

Page 59

background image

5-24

Continued

E.

Data

34

: Up/Down Function

Programming data " 34 " for

n39

(multi-function input terminal) allows the S4 / S5 inputs to be used

for Up/Down frequency setting.

NOTES:

1. Parameter

n38

will not be valid when

n39

is set to " 34 ".

2. Jog has priority over Up/Down.

3. Up/Down has priority over Multi-step Frequency inputs.

4. Upper limit speed is set by the formula:

n09

(Fmax) x

n30

(Freq. Ref. Upper Limit)

100

5. Lower limit speed is from

n31

, Frequency Reference Lower Limit.

6. See section 5.10 for information on the Up/Down hold memory.

EXAMPLE:

n39

Data

34

: Up/Down function

DRIVE

S4

UP

S5

DOWN

SC

0V

UP

o o

DOWN
o o

INPUT SIGNAL

Term. S4 Term. S5

FUNCTION

UP DOWN

Open

Open

HOLD

Closed Open

UP (Frequency command approaches frequency
command upper limit)

Open

Closed

DOWN (Frequency command approaches minimum
output frequency or frequency command lower limit,
whichever is larger)

Closed Closed

HOLD