26 table 5-3. multi-function output terminals – Yaskawa J7 Drive User Manual

Page 61

background image

5-26

Table 5-3. Multi-function Output Terminals

Set

Description

Value

Condition

Signal Level

0

Fault

Closed = Drive fault has occurred (except CPF0, CPF1)

1

During operation

Closed = Drive is operating

2

Speed at set frequency

Closed = Frequency Reference = output frequency

See paragraph 5.18A

3

Zero Speed

Closed = Drive is at zero Hz.

4

Frequency detection - low

Closed = Output frequency

n58

.

See paragraph 5.18B

5

Frequency detection - high

Closed = Output frequency

n58

.

See paragraph 5.18C

6

Overtorque detection

Closed = Overtorque detected

(N.O. contact)

See paragraph 5.19

7

Overtorque detection

Open = Overtorque detected

(N.C. contact)

See paragraph 5.19

10

Alarm (minor fault)

Closed = Alarm condition is present

11

During coast to stop

Closed = Drive output base block is active; motor is coasting

12

Local/Remote

Open = Frequency and Run Command by ext. input;
Closed = Frequency and Run Command by Digital Operator

13

Operation ready

Closed = Drive is ready for operation (not faulted)

14

Auto-restart

Closed = During auto-restart operation

15

During Undervoltage

Closed = Drive has an undervoltage fault or warning

16

During Reverse run

Closed = Drive operation in reverse

17

During Speed Search

Closed = Drive performing a speed search

18

Serial communication

Closed = Command from serial communication

n40

: Contact Output (external

terminals MA, MB, & MC)

A contact can be programmed to change states
during any of the conditions indicated in
Table 5-3.

5.18 MULTI-FUNCTION OUTPUT TERMINALS (Term. MA, MB, MC)

MULTI-FUNCTION
CONTACT OUTPUT
250Vac 1A OR LESS
30Vdc 1A OR LESS
(FACTORY SETTING
IS FOR SIGNAL
DURING OPERATION)

DRIVE

MA

MB

MC

o o

o o