beautypg.com

Yaskawa J7 Drive User Manual

Page 60

background image

5-25

Continued

FWD RUN

(S4) UP

COMMAND

(S5) DOWN

COMMAND

UPPER

LIMIT SPEED

LOWER

LIMIT SPEED

OUTPUT

FREQUENCY*

"SPEED AT SET

FREQUENCY"

SIGNAL

* U = UP (Accel) status; D = DOWN (Decel) status; H = HOLD (constant speed) status;

U1

= At Upper Limit Speed; D1 = At Lower Limit Speed

Up/Down Frequency Setting Timing

D1

D

D

D

H

H

H

H

H

H

H

U1

U

U

U

D1

D1

5.17 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S5)

F.

Data

16

: Accel/Decel Hold

By programming data " 16 " into one of the multifunction input parameters (

n36

thru

n39

), one of

the multi-function input terminals (S1 thru S5) becomes a HOLD command input. As long as the
HOLD command is present, accel and decel are in a prohibit state, and the output speed is held at
the level it was at the time the HOLD command was input. When the HOLD command is removed
while the system is still in Run condition, accel or decel will again become active to allow output to
reach set speed. If Stop is initiated while the HOLD command is present, the prohibit state is
cancelled and the system enters stop operation.

HOLD Function Timing

FWD RUN

HOLD CMD

SPEED REF.

OUTPUT SPEED