The Drive has the ability to have either a local or a remote reference and sequence selection.

Local -

Run and stop functions are controlled by the buttons on the digital operator (

n06

). The

frequency reference can come from a digital preset reference (

n21

&

n08

) or the

digital operator pot (

n07

).

Remote -

Run and stop functions are determined by parameter

n02

. The frequency reference is

determined by parameter

n03

.

Switching between local and remote is accomplished either by the LO/RE LED on the digital operator
or by the use of a multi-function input terminal programmed to data “

17

” (see paragraph 5.17A).

n02 : Operation Method Selection

Factory setting:

1

n03 : Reference Selection

Factory setting:

2

n06 : Stop Key Function

Factory setting:

0

Range: 0 or 1

SETTING

DESCRIPTION

0

Run and stop is controlled by the

and

buttons on the digital operator.

Run and stop is controlled by the multi-function input terminals
2-Wire control - Run Forward (

n36

thru

n39

is set to a data of “

1

”)

Run Reverse (

n36

thru

n39

is set to a data of “

2

”)

1

3-Wire control - Parameter

n37

needs to be set to a data of “

0

Run is controlled by a momentary closure on terminal S1
Stop is controlled by a momentary open on terminal S2
Forward/Reverse is controlled by terminal S3

2

Run and stop is controlled by serial communications

STOP

RESET

RUN

SETTING

DESCRIPTION

0

Frequency reference is controlled by the digital operator potentiometer.

1

Frequency reference is controlled by a digital preset speed (

n21

) and is affected by

n08

.

2

Frequency reference is controlled by the analog input terminal

FR

and is 0 - 10V DC

3

Frequency reference is controlled by the analog input terminals

FR

and is 4 - 20mA

4

Frequency reference is controlled by the analog input terminal

FR

and is 0 - 20mA

6

Frequency reference is controlled by serial communications.

SETTING

DESCRIPTION

0

key is effective at all times, regardless of programming of

n02

1

key is effective only when the run/stop command is from the digital operator

(n02 = 0)

STOP

RESET

STOP

RESET

5.13 LOCAL/REMOTE REFERENCE AND SEQUENCE SELECTION