beautypg.com

Super Systems 20PQ User Manual

Page 99

background image

95

Gr. 8

Run time group 8 [r.Hxx]
FEEDBACK POTENTIOMETER ADJUSTMENT

NOTE: The run time group 8 will be displayed only if the
instrument is in MANUAL mode.

- Feedback potentiometer adjustment
enabling - [r.H01]

This parameter is available only when close loop servomotor
output or open loop servomotor output with valve position
indication is configured.
Range: OFF = this selection disables the feedback

potentiometer calibration and the instrument will
come back to the first display of the run time
group 8.

On

= this selection starts the feedback potentiometer

adjustment.
NOTE: No time out will be applied during
feedback potentiometer calibration procedure.

- Servomotor low limit positioning - [r.H02]

This parameter is available only when feedback potentiometer
calibration enabling [r.H01] is equal to On.
Range: 0.0% to 100.0%
The middle display will show the valve position as a percentage
of the full input span.
By

s and t push-button it is possible to modify the valve

position.
When the desired initial position has been reached, push the
FUNC push-button.

- Feedback low limit calibration - [r.H03]

This parameter is available only when feedback potentiometer
calibration enabling [r.H01] is equal to On.
Range: OFF = To skip adjustment and hold the previous value

select OFF and then push FUNC

On

= To memorize the current position as feedback

low limit calibration select “On” and then push
FUNC

XKP-1-C2.p65

10/30/01, 9:37 AM

95