Super Systems 20PQ User Manual
Page 101

97
Gr. 9
Run time group 9 [r.Ixx]
TRACKING VALUES.
NOTES:
1) this run time group will be shown when the instrument
operates in programmer mode only.
2) The tracking function works even if no control output is
configured.
- Tracking group 1 - tracking above - [r.I01]
Lower display: t.A x
where x is the number of the tracking
group (from 1 to 10).
Range: from 1 to 500 digits.
NOTES:
1) The tracking above values will be added to the operative set
point value in order to obtain the high limit used for tracking
and guaranteed soak functions.
2) When a program is running and the tracking above value of
the segment in progress has been modified, the new value
will be immediately used.
- Tracking group 1 - tracking below - [r.I02]
Lower display: t.b x
where x is the number of the traking
group (from 1 to 10).
Range: from 1 to 500 digits.
NOTES:
1) The tracking below values will be subtracted to the operative
set point value in order to obtain the high limit used for
tracking and guaranteed soak functions.
2) When a program is running and the tracking below value of
the segment in progress has been modified, the new value
will be immediately used.
NOTE: For tracking group 2 to 10, the instrument will show on
the lower display the respective tracking group number and it is
possible to perform the same setting described for tracking
group 1.