beautypg.com

Super Systems 20PQ User Manual

Page 55

background image

51

CnF. 5

- Program restart tracking band - [C.G08]

This parameter will be available only when "St.Pr" (program
restart after power supply failure [C.G07]) is equal to “Src”.
Range: from 0 to 500 digits.

- Condition for output safety value - [C.G09]

This parameter will be available only when at least one control
output is configured.
Ranges:
- When no output is configured as open loop servomotor

control, "SF.Cn" can be set as follows:

Std.

= No safety value (“standard setting” see chapter

ERROR MESSAGES).

Ov.Un = Safety value applied when the instrument

detects an overrange or underrange condition
of the main input.

OvEr = Safety value applied when the instrument detects

an overrange condition of the main input.

Undr = Safety value applied when the instrument

detects an underrange condition of the main
input.

- When the open loop servomotor control is configured, "SF.Cn"

can be set as follows:

Std.

= No safety value (“standard setting” see chapter

ERROR MESSAGES).

Cnd.A = When the instrument detects an overrange or

underrange condition of the main input, the
servomotor is driven to its high limit position.

Cnd.b = When the instrument detects an overrange or

underrange condition of the main input, the
servomotor is driven to its low limit position.

Cnd.C = When the instrument detects an overrange or

underrange condition of the main input, the
action on servomotor is the complement of
“standard” setting.

- Output safety value - [C.G10]

This parameter will be available only when "SF.Cn" [C.G09] is
equal to “Ov.Un”, “OvEr” or “Undr”.
Range:
- from 0.0 % to 100.0 % if device is configured with one control

output;

- from -100.0 % to 100.0 % if device is configured with two

control outputs (split range excluded).

XKP-1-C2.p65

10/30/01, 9:37 AM

51