Super Systems 20PQ User Manual
Page 134

130
4) When the desired point has been reached, restart the
program.
NOTES:
1) When the JUMP function is activated, the central display will
show the same indication described for the RUN mode.
2) When the JUMP function is activated, the instrument modifies
the power output in accordance with the actual set point value
CONTOLLER MODE
During Controller mode the instrument operates as a standard
controller.
When it is desired to set the instrument in controller mode
proceed as follows:
1) put the instrument in STAND BY mode;
2) select the run time parameter group 2;
3) Select the "PrG" [r.B01] parameter and set NO;
4) push the FUNC pushbutton.
The PRG LED will be turned OFF.
When the instrument operates as controller all the break or timer
event outputs are deactivated and the run time parameter group
P and group 9 are not available while the SP parameter is
available.
When the transfert from programmer mode to controller mode is
required, the instrument will maintain the same PID parameters
used in STAND-BY mode.
During the controller mode, the standard features like alarms,
output failure detection function, serial link, manual mode and
lamp test are operative.
When the instrument operates in controller mode it is also
available the SMART function (self tuning of control param-
eters).