Super Systems 20PQ User Manual
Page 35

31
CnF. 1
8 = TC S
From - 50 to 1760
°C
9 = TC R
From - 50 to 1760
°C
10 = TC B
From
0 to 1820
°C
11 = TC G (or W)
From
0 to 2300
°C
12 = TC D (or W3)
From
0 to 2300
°C
13 = TC C (or W5)
From
0 to 2300
°C
14 = TC Ni-Ni18%Mo From
0 to 1100
°C
* 15 = RTD Pt100
From -200 to
850
°C
16 = TC L
From -150 to 1650
°F
17 = TC J
From -150 to 1830
°F
18 = TC K
From -150 to 2500
°F
19 = TC T
From -330 to
750
°F
20 = TC U
From -330 to 1110
°F
21 = TC E
From -150 to 1470
°F
22 = TC N
From -150 to 2550
°F
23 = TC S
From - 60 to 3200
°F
24 = TC R
From - 60 to 3200
°F
25 = TC B
From
32 to 3300
°F
26 = TC G ( or W)
From
0 to 4170
°F
27 = TC D (or W3)
From
0 to 4170
°F
28 = TC C (or W5)
From
0 to 4170
°F
29 = TC Ni-Ni18%Mo From
0 to 2000
°F
* 30 = RTD Pt100
From -330 to 1560
°F
31 = Linear
From
0 to
20 mA
32 = Linear
From
4 to
20 mA
33 = Linear
From
0 to
5
V
34 = Linear
From
1 to
5
V
35 = Linear
From
0 to
10
V
36 = Linear
From
2 to
10
V
37 = Linear
From
0 to
60 mV
38 = Linear
From
12 to
60 mV
* For these ranges it is possible to select a read-out with one
decimal figure but the instrument could not display a measure
lower than -199.9 or higher than 999.9 and the input range
will be limited by it.
NOTES:
1) When a linear input is selected, the instrument automatically
sets the "readout initial scale value" [C.d05] equal to 0 and
the "readout full scale value" [C.d06] equal to 4000
2) When input type has been changed, the instrument
automatically forces:
- the "ñ.In.L" [C.d05], "SS.th" [C.I09] and "brG.L" [C.I03]
parameters to the new initial scale value,
- the "ñ.In.H" [C.d06] and "brG.H" [C.I04] parameter to the
new full scale value and
- the "ñ.In.d" [C.d03] parameter to "no decimal figure".
XKP-1-C2.p65
10/30/01, 9:37 AM
31