A. 7
- turned OFF the bargraph displays (MKC only);
- sets analog retransmissions to the retransmitted initial
scale value;
- sets alarms in no alarm condition;
- sets events to OFF;
- disables the serial link;
- the time out will be removed.
2) When the modify mode is disabled by V101 (SW3), the
s or
t push-button pressure has no effect.
Push MENU pushbutton again and select the:
Default
configuration and user parameter setting group [C.Cxx]
Upper display: ConF
Ranges: tb.1
=load the default configuration parameters of the
table 1 (European)
tb.2
=load the default configuration parameters of the
table 2 (American)
LOAd =load the user setting (all run time and
configuration parameters)
SAVE=save the current setting of the run time and
configuration parameters (as user default
setting)
Lower display: dFlt
when "Tb.1" or "Tb.2" is selected
USEr
when "LOAd" or "SAVE" is selected
Push MENU pushbutton again.
The central display will show:
and then the display will show:
The default parameter loading procedure is ended.
The following is a list of the default configuration parameters of
tb 1 and tb 2:
TABLE 1
Configuration group 1 [C.dxx]
PARAM.
VALUE
NOTES
Ln.Fr
50
Hz
ñ.In.t
3
TC K with °C
ñ.In.d
----.
(No decimal figure)
ñ.In.S
dIS
Disabled
ñ.In.L
- 100
°C
ñ.In.H
1370
°C
OFSt
0
°C
dS.FL
0
(No filter)