beautypg.com

Super Systems 20PQ User Manual

Page 20

background image

16

3) The EIA standard establishes that by RS-485 interface it is

possible to connect up to 30 devices with one remote master
unit.
The serial interface of these instruments is based on “High
input impedance” transceivers; this solution allows you to
connect up to 127 devices (based on the same transceiver
type) with one remote master unit.

21

20

COMMON

22

B'/B

B/B'

A/A'

A'/A

M

A
S
T
E
R

I

N
S

T

R
U

M

E
N
T

F) SERIAL INTERFACE

Fig. 17 - RS-485 WIRING
The cable length must not exceed 1.5 km at 9600 BAUD.
NOTES:
1) This is an isolated RS-485 serial interface.
2) The following report describes the signal sense of the voltage

appearing across the interconnection cable as defined by
EIA for RS-485.
a) The ” A ” terminal of the generator shall be negative with
respect to the ” B ” terminal for a binary 1 (MARK or OFF) state.
b) The ” A ” terminal of the generator shall be positive with
respect to the ” B ” terminal for a binary 0 (SPACE or ON).

XKP-1-C2.p65

10/30/01, 9:36 AM

16