Calibration parameter errors
The instrument will show on the lower display one of the
following indications:
ñ.I.tc

= main thermocouple input calibration error

ñ.I.CJ

= cold junction compensation error

ñ.I.rt

= main RTD input calibration error

ñ.I.ñA

= main mA input calibration error

ñ.I.5

= main 5V input calibration error

ñ.I.10

= main 10 V input calibration error

A.I.ñA

= auxiliary mA input calibration error

A.I.5

= auxiliary 5V input calibration error

A.I.10

= auxiliary 10 V input calibration error

In.Ct

= current transformer input calibration error

FEEd

= electrical feedback input calibration error

05.ñA

= output 5 mA calibration error

06.ñA

= output 6 mA calibration error

When one of these errors is detected, contact your supplier.

Other errors

When during a program execution, a power failure occurs, at
power up the instrument displays this situation showing on the
upper display "E.600" indication.
Push one pusbutton to delete the "E.600" indication.

The instrument is also capable to detect the following errors:
E.100

Error during data saving in FRAM

E.110

Error in FRAM handling

E.500

Error during auto-zero measurement

E.501

Error during zero integrator measurement

E.502

Error during reference junction measurement. NOTE:
this error may be generated by an ambient temperature
higher than 70 °C (158 °F) or lower than -20 °C (-4 °F).

When one of these errors is detected, contact your supplier.

Two errors, related with the preliminary hardware setting, are
detectable:
3.

wrong position of the V301 dip switch.

8.

wrong position of the V101 dip switch.

When one of these error is detected, the display blanks and the
error code is shown on most significant digit of the upper
display.
Remake V101 or V301 setting.