- Time out for the soft start - [r.E16]
This parameter is available when at least one output is
configured as control output and no logic input is configured as
“Output limiter activator”.
Range: from 1 to 540 min.
Above this value the display shows “InF” and the limiting action
is always active.
NOTE: The tOL can be always modified but the new value will be
used only at the next device power up
- External control for AUTO /MANUAL mode
- [r.E17]
This parameter is available when one of the logic inputs is
configured for Auto/Manual selection and no program is running.
Range: On
the Auto/Manual selection is made by logic input
only
OFF
the Auto/Manual selection is made by “Man” key
or serial link only.
- External control for reverse/direct output
action selection - [r.E18]
This parameter is available when one of the logic inputs is
configured for direct/reverse output action selection.
Range: On
the reverse/direct selection is made by external
contact only
OFF
the reverse/direct selection is made by “Cn.Ac”
[r.d08] parameter or serial link only.
- Group 5 default data loading - [r.E19]
Range: OFF = No loading data
ON = Loading data