99

Gr. Hd

Run time group "Hd" [r.Mxx]
HIDDEN PARAMETERS - SMART LIMITS

NOTE: This group is accessible from every group (exception
made for P group) by keeping depressed the “MENU” key for 8
seconds.

- Minimum value of proportional band
calculated by SMART algorithm - [r.M01]

This parameter is available only when smart function is
configured (“Sñ.Fn” [C.G01] = “Enb”)
Range: From 0.5% to “Pb.Hi” [r.M02].
NOTE: The “Pb.Lo” resolution will be equal to 0.1% up to 10.0%
and 1% up to 999.0%.

- Maximum value of proportional band
calculated by SMART algorithm - [r.M02]

This parameter is available only when smart function is
configured (“Sñ.Fn” [C.G01] = “Enb”)
Range: from “Pb.Lo” [r.M01] to 999.0%
NOTE: The “Pb.Hi” resolution will be equal to 0.1% up to 10.0%
and 1% up to 999.0

- Minimum value of integral time calculated by
SMART algorithm - [r.M03]

This parameter is available only when smart function is
configured (“Sñ.Fn” [C.G01] = “Enb”)
Range: from 00.01 mm.ss to “ti.Hi” [r.M04].

- Maximum value of integral time calculated by
SMART algorithm - [r.M04]

This parameter is available only when smart function is
configured (“Sñ.Fn” [C.G01] = “Enb”)
Range: from “ti.Lo” [r.M03] to 20.00 mm.ss