Super Systems 20PQ User Manual
Page 88

84
Gr. 5
- Set point high limit - [r.E13]
Range: from rL [r.E12] to “ñ.In.H” [C.d06].
NOTES: Whenever “ñ.In.H” [C.d06] has been modified, the
following occurs:
1) rH will be realigned to it;
2) if the set point values are out of the new limits, "rH"
automatically assumes the default value.
- Rate of change for positive set point
variations - [r.E14]
Range: from 1 to 200 digits per minute.
Above this value the display shows “Inf” and the transfer will be
a step change.
- Rate of change for negative set point
variations - [r.E15]
Range: from 1 to 200 digits per minutes.
Above this value the display shows “Inf” and the transfer will be
a step change.
will be ignored and the output will step up to the value set by
“Añ.UL” [C.G04] parameter.
- Secondary output cycle time - [r.E11]
This parameter is available when a time proportional secondary
control output is configured.
Range: from 1 to 200 s
- Set point low limit - [r.E12]
Range: From “ñ.In.L” [C.d05] to rH [r.E13].
NOTES: Whenever “ñ.In.L” [C.d05] has been modified, the
following occurs:
1) rL will be realigned to it;
2) if the set point values are out of the new limits, "rL" automati-
cally assumes the default value.