Gr. P
from -100.0 to 100.0 % if the devices is configured with
two control outputs (split range excluded).
- Set point at the end of program 1 - [r.A16]
This parameter is available only when the selected program is
not running, it is not a linked program and "Control type at the
end of the program 1" [r.A14] is equal to ñSP.
Upper display: Pr.xx
where xx is the number of the selected
program
Range: from rL (set point low limit [rE.12]) to rH set point high
limit [rE.13]).
- PID group at the end of program 1 - [r.A17]
This parameter can be modified only when the selected program
is not running, it is not a linked program and at least one control
output is configured.
Upper display: Pr.xx
where xx is the number of the selected
program
Range: from 0 to 5
NOTE: setting ñPID equal to 0, the instrument will
maintain the PID values selected for the last program
segment.
- Program 1 - Timer event 1 - Step 1 - [r.A18]
This parameter can be modified only when the selected program
is not running, it is not a linked program and the specific timer
event is configured.
Upper display: On.h or On.ñ
where
On shows that during the first step the
relative output will be in ON
condition;
h
shows that the time base is
expressed in hours and minutes;
ñ
shows that the time base is
expressed in minutes and seconds.
NOTE: the time base of the timer event is equal to the "soak
time eng. unit" selection [r.A02].
Lower display: t.xx.y
where
xx
shows the event number
y
shows the step number
Range: from 0 to 99.59
Above this value the display will show "End" and this
step and all the next steps are deleted and the timed
event is ended.