Super Systems 20PQ User Manual
Page 76

72
Gr. 3
tHU
=
Thursday
Fri
=
Friday
Sat
=
Saturday
SUn
=
Sunday
NOTE: this is a readable parameter only and it cannot be
modified.
- Group 2 default data loading - [r.b09]
Range: OFF = No loading data
ON = loading data
Run time group 3 [r.Cxx]
ALARM THRESHOLD AND HYSTERESIS VALUE
- Manual reset of the alarms - [r.C01]
Range: ON/OFF
Change to ON and then depress “FUNC” key to reset/
acknowledge the alarm condition.
NOTES:
1) The reset/acknowledge function is always enabled.
2) When one of the logic input is configured as alarm reset, both
actions (from keyboard and from logic input) are active.
- Alarm 1 threshold - [r.C02]
This parameter is available when alarm 1 is configured as
process, deviation, main control output or secondary control
output alarm (“A1.tP” [rF.01] = “Proc” or “dEV” or “ñAin” or
“SECn”)
XKP-1-C2.p65
10/30/01, 9:37 AM
72
- Bazooka Probe (10 pages)
- Gold Probe (16 pages)
- HP2000 With 9100 Controller (10 pages)
- HP15 (23 pages)
- SuperOX (14 pages)
- PGA3000 (16 pages)
- PGA3500 (26 pages)
- e-TRIM (27 pages)
- 9120 with TS (80 pages)
- MGA6000 (42 pages)
- DP2000 (17 pages)
- DPC3500 (5 pages)
- MGA6010 (54 pages)
- DPC2530 (17 pages)
- Simple Dew (18 pages)
- DPL4000 (16 pages)
- H2 Sensor (17 pages)
- Hydrogen Nitrider Analyzer (12 pages)
- PH2 (19 pages)
- AC20 Quick Start (5 pages)
- XGA Viewer (46 pages)
- AC20 RS485 Modbus (62 pages)
- AC20 (114 pages)
- 20Q Calibration Manual (9 pages)
- CAT-100 (51 pages)
- 7EK 31080 (32 pages)
- 7EK 31082 Calibration Manual (5 pages)
- 7EK 31081 (36 pages)
- 7EK 31082 (34 pages)
- X5 Calibration Manual (1 page)
- 20Q (126 pages)
- 7SL (36 pages)
- X5 (74 pages)
- 9000 Series (15 pages)
- 3L Series (54 pages)
- 9015 Series (11 pages)
- 3 Series (92 pages)
- 9010 Series (66 pages)
- 9210 Series (65 pages)
- 9130 Series (174 pages)
- PC Configurator 2 Quick Start (15 pages)
- 9100 RPS (10 pages)
- 9125 Series (235 pages)
- 9120 RPS (11 pages)