Super Systems 20PQ User Manual
Page 67
![background image](https://www.manualsdir.com/files/806348/content/doc067.png)
63
CnF. 6
- Out failure detection (OFD) - [C.I11]
This parameter will be available only when the option is fitted
and the main and/or the secondary output is configured as time
proportional control output
Range: nonE = Function not used
ñC.On = Set “Fd.Fn” to “ñC.On” when the load under test
is energized during the ON status of the main
output (relay energized or SSR output status 1).
ñC.OF = Set “Fd.Fn” to “ñC.OF” when the load under
test is energized during the OFF status of the
main output (relay de-energized or SSR output
status 0).
SC.On= Set “Fd.Fn” to “SC.On” when the load under test
is energized during the ON status of the second-
ary output (relay energized or SSR output status
1).
SC.OF= Set “Fd.Fn” to “SC.OF” when the load under test
is energized during the OFF status of the second-
ary output (relay de-energized or SSR output
status 0).
NOTE: When the option is not fitted the middle display will show
“no.Pr”
- Primary current of the current transformer
- [C.I12]
This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range: From 10 A to 100 A
- Out failure detection - output assignment
- C.I13
This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range: nonE = The "Out failure detection" alarm is signalled
only on display
OUt.1 = The "Out failure detection" alarm is signalled
on OUT 1
OUt.2 = The "Out failure detection" alarm is signalled on
OUT 2
OUt.3 = The "Out failure detection" alarm is signalled on
OUT 3
OUt.4 = The "Out failure detection" alarm is signalled on
OUT 4
NOTE: "Out failure detection "alarm annunciator cannot be
assigned to an output already configured as control output.
XKP-1-C2.p65
10/30/01, 9:37 AM
63