Super Systems 20PQ User Manual
Page 90

86
Gr. 6
Run time group 6 [r.Fxx]
ALARM SETTING
- Alarm 1 type - [r.F01]
This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range: Proc = Alarm on process variable
bAnd = Band alarm on process variable
dEV
= Deviation alarm on process variable
ñAin = Alarm on Main control output value
SECn = Alarm on Secondary control output value
NOTE: When alarm type has been changed the alarm threshold
will be forced to its default value and alarm status will be
deleted.
- Alarm 1 configuration - [r.F02]
This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range: H.A.
= High alarm (outside band) with automatic reset
L.A.
= Low alarm (inside band) with automatic reset
H.A.Ac= High alarm (outside band) with automatic reset
and acknowledge
L.A.Ac= Low alarm (inside band) with automatic reset
and acknowledge
H.L.
= High alarm (outside band) with manual reset
L.L.
= Low alarm (inside band) with manual reset
NOTE: When alarm configuration has been changed, the alarm
status will be deleted.