Super Systems 20PQ User Manual
Page 49

45
CnF. 3
- Main output auxiliary conditioning - [C.F11]
This parameter will be available only when main control output is
configured and “ñC.Cn” ("Main control output conditioning"
[C.F06]) is different from “norñ”.
Range: bEFr = The functions listed at Note (*) are calculated
before to apply the action selected by “ñC.Cn”
("Main control output conditioning" [C.F06])
parameter.
AFtr
= The functions listed at Note (*) are calculated
after to apply the action selected by “ñC.Cn”
(“Main control output conditioning” [C.F06])
parameter.
Note (*)
- "Main control output limiters" - for more details see [r.E04]
and [r.E05] parameters.
- "Main control output max rate of rise" (see [r.E06]).
- "Control output display value" - for more details see "Display
function during programmer mode" paragraph at pag. 106
and [C.F07], [C.F08], [C.F09] and [C.F10] parameters.
- "Threshold for alarm on control output value" - for more
details see [r.F01], [r.F05] [r.F09] and [r.F13] parameters.
- The control output value displayed by bargraph.
- Secondary control output conditioning
- [C.F12]
This parameter will be available only when secondary control
output is configured.
Range: norñ
= The control output is calculated by the PID
CñPL = The control output is complemented (100-PID
calculated value)
Ouic
= The control output is conditioned to match a
“QUICK OPENING” flow characteristic
Eou
= The control output is conditioned to match an
“EQUAL PERCENTAGE” flow characteristic
For more details see also NOTE about output conditioning at
page 44.