beautypg.com

3 analogue inputs, 4 analogue outputs, 4function description – Pilz PMCprotego D.72/000/0/0/2/208-480VAC User Manual

Page 82: 4 expansion cards

background image

4.4

Expansion cards

4

Function Description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-48

4.4.3.3

Analogue inputs

Analogue inputs

4-

][Funktion_Erw_PosI_O_AI

Functions:

The expansion card PosI/O-AIO has 2 analogue voltage inputs (ANA-

LOG-IN3, ANALOG-IN4) for specifying setpoint values.

Differential inputs, signal range from -10 VDC to +10 VDC.

Resolution (with sign bit): 16 Bit

Parameter setting:

A list of the pre-programmed functions is available in the “Digital I/O”

window of the PDrive commissioning software.

][Funktion_Ein_Aus_Param_neu

If a pre-programmed function has been newly assigned, the data

record must be stored in the servo amplifier's EEPROM and the unit

must be reset (e.g. using the commissioning software).

4.4.3.4

Analogue outputs

Analogue outputs

4-

][Funktion_Erw_PosI_O_AO

Functions:

The expansion card PosI/O-AIO has 2 analogue voltage outputs (AN-

ALOG-OUT1, ANALOG-OUT2). Digital measured values recorded in

the servo amplifier can be output.

Signal range from -10 VDC to +10 VDC.

Resolution (with sign bit): 16 Bit

Parameter setting:

A list of the pre-programmed functions is available in the “Digital I/O”

window of the PDrive commissioning software.

][Funktion_Ein_Aus_Param_neu

If a pre-programmed function has been newly assigned, the data

record must be stored in the servo amplifier's EEPROM and the unit

must be reset (e.g. using the commissioning software).

This manual is related to the following products: