EMC-compliant wiring

6

Wiring

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-14

Reduce a device's high frequency disturbances. These disturbances

are emitted via the the mains cable or via emissions from the mains

cable. The noise suppression filters limit the noise emissions to a

specified amount.

Filters have leakage currents which may be considerably greater than

the rated values in the event of a fault (phase failure, unbalanced load)

(see section entitled “Leakage current”).

Please note the following if additional filter measures are required:

Earth the filter to avoid hazardous voltages

Leakage currents are high frequency disturbances, so earth the filter

at low impedance over a wide area.

][EMV_Wohnumgebung

6.5.4

Chokes

Chokes

6-

][EMV_Drosseln

If motor cables are > 25 m, a choke must be used on the servo amplifi-

er's output.

The choke is used to:

Reduce the level of interference on the motor cable

Deal with EMC problems retrospectively

Protect the semiconductor on the inverted rectifier in the case of an

earth fault or short circuit

Protect the motor from high voltage rise rates

Additional earthing measures are unnecessary because, unlike filters,

chokes do not have to divert disturbances to earth.

][Funktion_Netzspannung_Drossel

WARNING!

In a residential environment this product may cause high-fre-

quency noise, so that suppression measures may be required.

INFORMATION

A 3L line choke with u

k

= 2% must be used in the event of a

mains voltage imbalance of > 3%. Install the line choke on the

mounting plate in a way that is EMC-compliant.