Notes on wiring

6

Wiring

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-6

Please note the following safety guidelines:

][Verdr_nie_unter_Spg_1_D_48_72

][Verdr_nie_unter_Spg_2

6.3.1

Contact protection

Contact protection

6-

6.3.1.1

Leakage current

Leakage current

6-

][Verdr_Ableitstrom

The leakage current via the protective earth conductor is the sum of the

leakage currents from the units and cables.

The frequency of the leakage current is made up of a number of frequen-

cies. The residual current devices evaluate the 50 Hz current. It's not

possible to measure the leakage currents using a conventional multim-

eter because these too are standardised at 50 Hz current.

DANGER!

Risk of electrocution!

Never unplug the electrical connections on the servo amplifier

while voltage is applied.

Switch off the supply voltages!

Residual charges in the capacitors may still show hazardous val-

ues for up to 10 min. after the mains voltage is switched off.

Measure the voltage on the intermediate circuit (+DC/-DC). Wait

until the voltage has dropped below 40 VDC.

Wait at least 10 minutes before touching any parts that carry

voltage (e.g. contacts) or loosening the connections.

DANGER!

Risk of electrocution!

Never wire the electrical connections on the servo amplifier

while voltage is applied.

Switch off the mains voltages and 24 V supply!

Make sure that the control cabinet is made safe, e.g. through an

access lock or warning signs. Do not switch on the voltages until

the system is commissioned!