4function description, 2 power element – Pilz PMCprotego D.72/000/0/0/2/208-480VAC User Manual
Page 38

4.2
Power element
4
Function Description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-4
Connection via isolating transformer
400 – 480 V mains supplies without earthed star point (asymmetrically
earthed or unearthed mains supplies), see Fig. (7) – (11)
Requirements for isolating transformers
An earthed star point must be available on the secondary side. The
star point on the secondary side must be earthed and must be con-
nected to the servo amplifier's protective earth conductor. This will
prevent overvoltages between the external conductors and the servo
amplifier housing.
The isolating transformers must have the relevant input and output
voltages.
Netzdrossel
Line choke
][Funktion_Netzspannung_Drossel
][Funktion_Netzspannung_Anschluss_protego_D
The following illustration shows the connection types.
INFORMATION
A 3L line choke with u
k
= 2% must be used in the event of a
mains voltage imbalance of > 3%. Install the line choke on the
mounting plate in a way that is EMC-compliant.