Technical data – Moniteur 50 Series SMART Positioners User Manual
Page 99
Technical Data
6-1
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Technical Data
General data: basic instrument 6DR400x–xx (without PROFIBUS PA) and 6DR410x–xx
(with PROFIBUS PA)
Climatic category IEC 721
Storage
1K5 but – 40
°
C to + 80
°
C
1)
Transport
2K4 but – 40
°
C to + 80
°
C
1)
Operation without purging air
3K3 but – 30
°
C
3)
to + 80
°
C
2)
with purging air
3K4 but – 30
°
C
3)
to + 80
°
C
2)
Degree of protection
IP65 acc. to EN60529
Dimensions
plastic housing
see Fig. 3-2
metal housing
see Fig. 3-4
Weight
basic instrument
plastic
approx 0.9 kg
metal
approx. 1.3 kg
Resistance to vibration
5 g acc. to IEC 48–2–6 with NAMUR mount-
ing
8 g (10 g) acc. to IEC 48–2–6 with ARCA
mounting or “rotary actuator”
4)
Termination system
electrical signals
screw terminals 1.5 AWG14
cable gland PG 13
pneumatic signals
internal thread G 1/4 DIN 45141
Mounting position
any, outlet air opening and controller output
axis not upwards
Material
housing
plastic
fibre–glass reinforced polyester
metal
anodized Gk–Al Si 7Mg
pneumatic connection block
for plastic housing
anodized Al Mg Si < 6
CE symbol
conforms to EMC directive 89/336 EEC in
accordance with the following standards
Emitted interference
EN 50 081–1
Immunity to interference
EN 50 082–2 and NAMUR NE21 May 93
1)
When commissioning at
v
0
°
C, ensure the valves are purged with the dry medium for a sufficiently long period
2)
See technical data for basic instrument and option for ex-proof instruments
3)
Reduced refresh rate of the LCD display below –10
°
C
4)
To 100 Hz
6