Operation

4-18

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

Example:
YNRM = FLOW with YA = 10 % and YE = 80 %

YNRM = MPOS or YNRM = FLOW
Default: YA = 0% and YE = 100%

Input current
(Setpoint)

Input current
(Setpoint)

Input current
(Setpoint)

X display
W display

X display
W display

X display
W display

Mechan. travel
(readback)

Mechan. travel
(readback)

Mechan. travel
(readback)

0mm

0mm

0mm

80mm

80mm

80mm

16mm

16mm

16mm

32mm

32mm

32mm

48mm

48mm

48mm

64mm

64mm

64mm

20mA

20mA

20mA

4mA

4mA

4mA

7.2mA

7.2mA

7.2mA

10.4mA

10.4mA

10.4mA

13.6mA

13.6mA

13.6mA

16.8mA

16.8mA

16.8mA

0%

0%

0%

100%

100%

100%

20%

20%

20%

40%

40%

40%

50%

50%

50%

60%

60%

60%

80%

80%

80%

YE = 80%

YE = 80%

YE = 100%

YA = 10%

YA = 10%

YA = 0%

Example:
YNRM = MPOS with YA = 10 % and YE = 80 %

Fig. 4-10

Dependence of travel on normalization and YA and YE as shown by an 80 mm linear actuator.

Tight closing with manipulated variable

With this function the valve can be moved to its seat with maximum
actuating power (maintained contact of the piezovalves). The tight clo-
sing function can be activating on one side only or for both end posi-
tions. YCLS is activated when the setpoint is below 0.5 % or above
99.5% of the setpoint flow.

Wert für Dichtschließen unten

Wert für Dichtschließen oben

34.YCLS

35.YCDO

36.YCUP