Operation
4-18
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Example:
YNRM = FLOW with YA = 10 % and YE = 80 %
YNRM = MPOS or YNRM = FLOW
Default: YA = 0% and YE = 100%
Input current
(Setpoint)
Input current
(Setpoint)
Input current
(Setpoint)
X display
W display
X display
W display
X display
W display
Mechan. travel
(readback)
Mechan. travel
(readback)
Mechan. travel
(readback)
0mm
0mm
0mm
80mm
80mm
80mm
16mm
16mm
16mm
32mm
32mm
32mm
48mm
48mm
48mm
64mm
64mm
64mm
20mA
20mA
20mA
4mA
4mA
4mA
7.2mA
7.2mA
7.2mA
10.4mA
10.4mA
10.4mA
13.6mA
13.6mA
13.6mA
16.8mA
16.8mA
16.8mA
0%
0%
0%
100%
100%
100%
20%
20%
20%
40%
40%
40%
50%
50%
50%
60%
60%
60%
80%
80%
80%
YE = 80%
YE = 80%
YE = 100%
YA = 10%
YA = 10%
YA = 0%
Example:
YNRM = MPOS with YA = 10 % and YE = 80 %
Fig. 4-10
Dependence of travel on normalization and YA and YE as shown by an 80 mm linear actuator.
Tight closing with manipulated variable
With this function the valve can be moved to its seat with maximum
actuating power (maintained contact of the piezovalves). The tight clo-
sing function can be activating on one side only or for both end posi-
tions. YCLS is activated when the setpoint is below 0.5 % or above
99.5% of the setpoint flow.
Wert für Dichtschließen unten
Wert für Dichtschließen oben
34.YCLS
35.YCDO
36.YCUP