Technical Data

6-2

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

General data: basic instrument 6DR400x–xx and 6DR410x–xx

AD converter

Sampling time

12.5 ms

Resolution

v

0.05 %

Transmission error

v

0.2 %

Temperature influence

v

0.1 % / 10 K

Controller data

5–step switch

adaptive

Dead zone

dEbA = Auto

adaptive or

dEbA = 0.1 to 10 %

fixed setting

Controllable actuating times

w

1.5 s

Pneumatic and mechanical data: basic instrument 6DR400x–xx and 6DR410x–xx

Power supply (inlet air)

Medium

Instrument air, free of oil, water, and dust

Pressure

1.4 to 7 bar

Solids content

< 30

µ

m

Dewpoint

20 K below the lowest ambient temperature

Unrestricted flow

Inlet air valve

5.5 Nm

3

/h with a drop in pressure from 6 to

5 bar

Valve leakage

< 6

10

–4

Nm

3

/h

Restrictor ratio

adjustable up to

: 1

Air consumption in settled state

< 3.6

10

–2

Nm

3

/h

Types of actuators

Single and double acting (not with
6DR4001–xx)

Positioning times

1.5 to 150 s

Linear actuators

Mounting kit 6DR4004–8V and –8L

acc. to IEC 534–6 (NAMUR)

Linear range

3 to 130 mm (rotation angle on the controller
output axis from 16

°

to 90

°

)

Rotary actuators

Mounting kit 6DR4004–8D

Angle of rotation

30

°

to 100

°