Moniteur 50 Series SMART Positioners User Manual
Page 100
Technical Data
6-2
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
General data: basic instrument 6DR400x–xx and 6DR410x–xx
AD converter
Sampling time
12.5 ms
Resolution
v
0.05 %
Transmission error
v
0.2 %
Temperature influence
v
0.1 % / 10 K
Controller data
5–step switch
adaptive
Dead zone
dEbA = Auto
adaptive or
dEbA = 0.1 to 10 %
fixed setting
Controllable actuating times
w
1.5 s
Pneumatic and mechanical data: basic instrument 6DR400x–xx and 6DR410x–xx
Power supply (inlet air)
Medium
Instrument air, free of oil, water, and dust
Pressure
1.4 to 7 bar
Solids content
< 30
µ
m
Dewpoint
20 K below the lowest ambient temperature
Unrestricted flow
Inlet air valve
5.5 Nm
3
/h with a drop in pressure from 6 to
5 bar
Valve leakage
< 6
10
–4
Nm
3
/h
Restrictor ratio
adjustable up to
∞
: 1
Air consumption in settled state
< 3.6
10
–2
Nm
3
/h
Types of actuators
Single and double acting (not with
6DR4001–xx)
Positioning times
1.5 to 150 s
Linear actuators
Mounting kit 6DR4004–8V and –8L
acc. to IEC 534–6 (NAMUR)
Linear range
3 to 130 mm (rotation angle on the controller
output axis from 16
°
to 90
°
)
Rotary actuators
Mounting kit 6DR4004–8D
Angle of rotation
30
°
to 100
°