Preparing for Operation

3-13

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

3.4.2 Connection variants not protected from explosion hazard (devices

with PROFIBUS PA)

!

Warning

The applicable regulations for electrical installation must be observed,
in particular, in zones subject to explosion hazard

the regulation about electrical equipment in zones subject to explo-
sion hazard. The erection guidelines of the country in question must
be observed.

the regulation about erection of electrical equipment in zones sub-
ject to explosion hazard (DIN VDE 0165)

the certificate of conformity

It is necessary to check whether the auxiliary power supplied by the
coupler matches the value specified on the rating plate of the SI-
PART PS2 PA and in the Ex certification.

If the intrinsically safe version is operated with an operating voltage of
more than 24 V by mistake, the device must no longer be used for in-
trinsically safe applications.

The positioner is powered via the PROFIBUS PA by the DP/PA coupler
or DP/PA link. The devices draw their electrical auxiliary power from a
power supply unit with SELV (safety extra–low voltage).

Note

The following generally applies to laying the bus cable:

Lay cables separated from cables carrying > 60 V

Avoid the vicinity of large electrical equipment

Only use recommended cable types

The specifications only apply to properly installed equipment

Only use a shielded, two–conductor cable as the bus cable.
The recommended cable types are:
Ex i applications:

Siemens 6XV1 830–5AH01 (color blue)

Non Ex applications:

Siemens 6XV1 830–5BH10 (color black)

The mechanical and electrical data of these two cable types are identi-
cal.

1. Strip back the bus cable insulation as shown in Fig.3-11.

2. Open the housing of the positioner by loosening the four screws of

the cover.

Assembling the
bus cable