beautypg.com

Operation 4-16 – Moniteur 50 Series SMART Positioners User Manual

Page 78

background image

Operation

4-16

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

Setpoint turning points (see Fig. 4-9)

Each setpoint turning point can be assigned a flow characteristic value
at intervals of 5%. These points produce a polygon consisting of 20
straight lines which results in an image of the valve characteristic
curve.

Setpoint turning points can only be entered when 8.SFCT = FrEE.

0

10

20

30

40

50

60

70

80

90

100 %

0

10

20

30

40

50

60

70

80

90

0

0

10

10

20

20

30

30

40

40

50

50

60

60

70

70

80

80

90

90

100

100

100 %

SP

w

YA = 12 %

YE = 96 %

8.SFCT = 1:50

8.SFCT = lin

8.SFCT = 1:25

33.YNRM =
MPoS

33.YNRM =
FLoW

[%]

[%]

SL0

SL2

SL4

SL6

SL8

SL10 SL12 SL14 SL16 SL18 SL20

12

22,5

33

43,5

54

64,5

75

85,5

96 %

w

MPoS

FLoW

8. SFCT = n1:25

Fig. 4-9

Setpoint characteristics, normalization of the manipulated variables and tight closing function

09.SL0 to 29.SL20