Operation
4-16
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Setpoint turning points (see Fig. 4-9)
Each setpoint turning point can be assigned a flow characteristic value
at intervals of 5%. These points produce a polygon consisting of 20
straight lines which results in an image of the valve characteristic
curve.
Setpoint turning points can only be entered when 8.SFCT = FrEE.
0
10
20
30
40
50
60
70
80
90
100 %
0
10
20
30
40
50
60
70
80
90
0
0
10
10
20
20
30
30
40
40
50
50
60
60
70
70
80
80
90
90
100
100
100 %
SP
w
YA = 12 %
YE = 96 %
8.SFCT = 1:50
8.SFCT = lin
8.SFCT = 1:25
33.YNRM =
MPoS
33.YNRM =
FLoW
[%]
[%]
SL0
SL2
SL4
SL6
SL8
SL10 SL12 SL14 SL16 SL18 SL20
12
22,5
33
43,5
54
64,5
75
85,5
96 %
w
MPoS
FLoW
8. SFCT = n1:25
Fig. 4-9
Setpoint characteristics, normalization of the manipulated variables and tight closing function