A-12 – Moniteur 50 Series SMART Positioners User Manual
Page 120
![background image](/manuals/698969/120/background.png)
A-12
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
209
58
FEEDBACK
Current position
ds33
1
r
1
0
Value
2
0x4f
Status
221
70
0
BIN_IN_1_FUNCT
Function of binary input 1
unsigned8
1
r, w
222
71
0
BIN_IN_2_FUNCT
Function of binary input 2
unsigned8
1
r, w
223
72
0
ALARM_FUNCT
Function of the alarm outputs
unsigned8
1
r, w
224
73
10.0
ALARM_1
Alarm value 1, with ref. to OUT_SCALE
float
1
r, w
225
74
90.0
ALARM_2
Alarm value 2, with ref. to OUT_SCALE
float
1
r, w
226
75
0
FAULT_FUNCT
Function of the fault signaling output
unsigned8
1
r, w
227
76
1
DELAY_TIME
Monitoring time for setting the
fault signal
float
1
r, w
228
77
0.1
TOLERANCE_BAND
Response threshold of the fault signal
float
1
r, w
229
78
1
TRAVEL_RATE_AUTO
Travel rate CLOSE automatic / manual
unsigned8
1
r, w
230
79
1
TRAVEL_RATE_INC_AUTO
Travel rate OPEN automatic / manual
unsigned8
1
r, w
231
80
1
DEADBAND_AUTO
Deadband automatic / manual
unsigned8
1
r, w
232
81
1
DELAY_TIME_AUTO
Monitoring time automatic / manual
unsigned8
1
r, w
233
82
1
TOLERANCE_BAND_AUTO
Response threshold automatic / manual
unsigned8
1
r, w
234
83
0
SETP_CUTOFF_ENA
Enable / disable tight closing
unsigned8
1
r, w
235
84
0
BINARY_STATUS
Status of the binary signals
unsigned8
1
r
236
85
0
TEST_ACTIVATE
Activate test functions
unsigned8
1
w
237
86
TEST_FUNCTION
Execute test functions
record
3
w
1
Command
unsigned8
1
2
Change_Flag
unsigned8
1
3
Parameter
octet_string
30
238
87
0
TEST_READ
Read test information
octet_string
32
r
239
88
DIAG1
float
3
r
1
0.0
Zero point_P0
Value of the pot voltage in % stop top
2
0.0
Final value_P100
Value of the pot voltage in % stop bottom
3
0.0
Leckage
in % / min
240
89
0
DIRECTION_CHANGE
Number of direction changes
unsigned32
1
r, w
251
100
VIEW_1
void
3
r
1
1
ST_REV
2
6
MODE_BLK
3
7
ALARM_SUM