Moniteur 50 Series SMART Positioners User Manual
Page 104
Technical Data
6-6
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Electrical data: options
6DR4004–8x
6DR4004–6x
Acc. to EN 50014 and
EN 50020
–
II2G EEx ib II C T4/T5/T6
2)
Place of installation
–
zone 1
Ambient temperature
– 30 to + 80
°
C
T4 – 30 to + 80
°
C
T5 – 30 to + 65
°
C
T6 – 30 to + 50
°
C
Alarm module
6DR4004–8A
6DR4004–6A
Binary outputs, A1, A2,
Signal state High
(not available)
+ 3 %
conductive R = 1 k
Ω
– 1 %
w
2.1 mA
1)
Signal state Low (available)
3)
blocked I
R
< 60
µ
A
v
1.2 mA
1)
Internal capacitance
C
i
–
4.7 nF
Internal inductance
L
i
–
negligible
Power supply U
H
v
+ 35 V
For connection to intrinsically
safe switching amplifiers to
DIN 19234 with
U
i
–
+30 V
Binary input BE2
Terminal 21/22
(electrically connected with
basic instrument)
basic instrument)
Signal state 0
isolated contact open
Signal state 0
Signal state 1
isolated contact o en
isolated contact closed
g
Contact load
3 V, 5
µ
A
Terminal 11/12
(electrically isolated)
Signal state 0
Signal state 1
Input resistance
Internal capacitance
Ci
Internal inductance
Li
For connection to intrinsically
safe voltage sources
with
U
i
v
4.5 V or open
w
13 V
w
25 k
Ω
negligible
negligible
v
30 V
Electrical isolation
to the basic instrument and
the 4 outputs among themsel-
ves
A1, A2, , BE2 (T. 11/12)
and the basic instrument are
isolated intrinsically safe cir-
cuits
Test voltage 50 Hz 1 min
500 V
rms