beautypg.com

Moniteur 50 Series SMART Positioners User Manual

Page 60

background image

Preparing for Operation

3-22

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

Initialization is largely automatic.

Open

Closed

up

down

Rotary actuator

Linear actuator

Fig. 3-21

Actuation direction of actuators

The initialization procedure is shown in the following flowchart
(Figs. 3-22 to 3-24).

Configuring

Inlet valve 1

max. 30 s open

y > 10 % ?

Outlet valve or
inlet valve 2 max. 30 s open

Ascertain
direction

Traverse the working
range of the actuator
with

yes

no

1

Potentiometer value
normalized manipulated variable [%]

RUN 1

y > 10 % ?

2

yes

no

> 5 s

Continue using:

Manual operation

Fig. 3-22

Initialization, part 1

Initialization