Moniteur 50 Series SMART Positioners User Manual
Page 66
![background image](/manuals/698969/66/background.png)
Setpoint ramp
Setpoint direction
Parameter name
Display
Function
Parameter values
Unit
Factory setting
Customer
setting
If "turn" is selected, you cannot set 33°
Parameter does not appear if 1.YFCT=turn has been selected
Turning points only appear wih selection 10.SFCT = FrEE
Alternatively "no" if initialization has not yet been carried out
NC contact means:
NO contact means:
Normal means:
High level without fault
Inverted means:
Low level without fault
1)
2)
3)
4)
5)
6)
Setpoint turning point at 0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
no / ##.#
Strt
0 MA
4 MA
riSE
FALL
0.0 to 100.0
0.0 to 100.0
AUto
0 to 400
AUto
0.1 to 10.0
Lin
1 : 25
1 : 50
FrEE
0.0 to 100.0
0.0 to 100.0
0.0 to 100.0
MPoS
FLow
no
uP:
:dW
uP:dW
no
Strt
oCAY
Response threshold of alarm
oFF
5 | 10 | 15 | 20
25 | 30 | 35
40 | 50 | 60 | 70 | 90 | 110 | 130
(short lever 33°)
(short lever 90°)
(long lever 90°)
90°
33°
3.YWAY 2)
1)
4.INIT
6.SDIR
7.SPRA
8.SPRE
9.TS
10.SFCT
11.SL0
12.SL1
13.SL2
14.SL3
15.SL4
16.SL5
17.SL6
18.SL7
19.SL8
20.SL9
21.SL10
22.DEBA
23.YA
24.YE
26.YCLS
5.SCUR
3)
5)
5)
6)
6)
25.YNRM
2.YAGL
1.YFCT
(example)
0 to 20 mA
4 to 20 mA
4)
rising
falling
on
uP
doW
StoP
-on
-uP
-doW
-StP
on
bLc1
bLc2
uP
doW
StoP
-on
-uP
-doW
-StP
normal
inverted
inverted
normal
mm
0.0
28.5
50.0
62.6
71.5
78.5
84.1
88.9
93.1
96.7
100.0
oCAY
AUto
s
%
%
10.0
90.0
oFF
oFF
oFF
riSE
no
MPoS
100.0
0.0
AUto
Lin
0
%
%
%
%
s
%
%
mA
100.0
0.0
riSE
4
%
AUto
oFF
Degrees
33°
WAY
no
NC
contact
NC
contact
No
contact
No
contact
Function of BI 1
Function of BI 2
Function of alarm output
action with opened switch or Low level
action with closed switch or High level
Initialization
Current range of setpoint
Setpoint for start of split range
Setpoint for end of split range
Dead zone of controller
Start of manipulated variable limiting
End of manipulated variable limiting
Standardization of
manipulated variable
Tight closing with manipulated variable
Without
Top only
Bottom only
Top and bottom
Leverage ratio (stroke range)
must match set leverage ratio on the actuator
Driver pin must be set to the value of the actuator
travel or, if this value is not scaled, to the next
larger scale value.
Rated angle of rotation of feedback
Type of actuator
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator
without sine correction)
Set transmission ratio selector (7) appropriately
(see view of device)
Setpoint function
Linear
Equal-percentage 1 : 25
Equal-percentage 1 : 50
Freely adjustable
To mech. travel
To flow
Rising
Falling
1)
2)
3)