Preparing for Operation

3-20

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

3.5

Pneumatic connection

!

Warning

For safety reasons the pneumatic power must only be input after
installation when the positioner is switched to operating level P manual
mode with the electrical signal applied (state of supply, see Fig. 4-2).

Note

Check the air quality! Industrial air, free of oil, solid content < 30

m

m, dew

point under pressure 20 K below the lowest ambient temperature.

If necessary connect the manometer block for inlet air pressure and
positioning pressure.

Connection using inside thread G 1/4 DIN 45141:

P

Z

inlet air 1.4 to 7 bar

Y1

positioning pressure 1 for single and double-acting actuators

Y2

positioning pressure 2 for double-acting actuators

E

air outlet (remove silencer if necessary)

Safety position in the event of electrical power failure

single acting:

Y1

vented

double acting:

Y1

max. positioning pressure
(inlet air pressure)

Y2

vented

Connect positioning pressures Y1 and Y2 (only for double-acting
actuators) in accordance with the required safety position.

Connect the inlet air to P

Z

.