Moniteur 50 Series SMART Positioners User Manual
Page 105
Technical Data
6-7
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
J
y
module
6DR4004–8J
6DR4004–6J
2-wire circuit
Nominal signal range
i
4 to 20 mA short circuit proof
Control range
3.6 to 20.5 mA
Power supply
U
H
+ 12 to 35 V
+ 12 to 30 V
External load
R
B
[k
Ω
]
v
(U
H
[V] – 12 V) / i [mA]
Transfer error
v
0.3 %
Effect of temperature
v
0.1 % / 10 K
Resolution
v
0.1 %
Residual ripple
v
1 %
Internal capacitance
C
i
–
v
10 nF
Internal inductance
L
i
–
0.2 mH
For connection to intrinsically
safe voltage sources
with
U
i
–
v
30 V
J
i
–
v
100 mA
P
i
–
v
1 W
Electrical isolation
to the basic instrument
J
y
(Kl. 61/62) and the basic
instrument are isolated intrin-
sically safe circuits
Test voltage 50 Hz 1 min
500 V
rms
1) Operating points with supply to DIN 19234 U
H
= 8.2 V; R
i
= 1 k
Ω
2) Only with the basic instrument 6DR4000–1E/–2E
3) The status is also Low if the basic instrument is faulty or without auxiliary power supply