Moniteur 50 Series SMART Positioners User Manual

Page 105

background image

Technical Data

6-7

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

J

y

module

6DR4004–8J

6DR4004–6J

2-wire circuit

Nominal signal range

i

4 to 20 mA short circuit proof

Control range

3.6 to 20.5 mA

Power supply

U

H

+ 12 to 35 V

+ 12 to 30 V

External load

R

B

[k

]

v

(U

H

[V] – 12 V) / i [mA]

Transfer error

v

0.3 %

Effect of temperature

v

0.1 % / 10 K

Resolution

v

0.1 %

Residual ripple

v

1 %

Internal capacitance

C

i

v

10 nF

Internal inductance

L

i

0.2 mH

For connection to intrinsically
safe voltage sources
with

U

i

v

30 V

J

i

v

100 mA

P

i

v

1 W

Electrical isolation

to the basic instrument

J

y

(Kl. 61/62) and the basic

instrument are isolated intrin-
sically safe circuits

Test voltage 50 Hz 1 min

500 V

rms

1) Operating points with supply to DIN 19234 U

H

= 8.2 V; R

i

= 1 k

2) Only with the basic instrument 6DR4000–1E/–2E

3) The status is also Low if the basic instrument is faulty or without auxiliary power supply