Example:
YNRM = FLOW with YA = 10 % and YE = 80 %
YNRM = MPOS or YNRM = FLOW
Default: YA = 0% and YE = 100%
Input current
(Setpoint)
Input current
(Setpoint)
Input current
(Setpoint)
X display
W display
X display
W display
X display
W display
Mechan. travel
(readback)
Mechan. travel
(readback)
Mechan. travel
(readback)
0mm
0mm
0mm
80mm
80mm
80mm
16mm
16mm
16mm
32mm
32mm
32mm
48mm
48mm
48mm
64mm
64mm
64mm
20mA
20mA
20mA
4mA
4mA
4mA
7.2mA
7.2mA
7.2mA
10.4mA
10.4mA
10.4mA
13.6mA
13.6mA
13.6mA
16.8mA
16.8mA
16.8mA
0%
0%
0%
100%
100%
100%
20%
20%
20%
40%
40%
40%
50%
50%
50%
60%
60%
60%
80%
80%
80%
YE = 80%
YE = 80%
YE = 100%
YA = 10%
YA = 10%
YA = 0%
Example:
YNRM = MPOS with YA = 10 % and YE = 80 %
Fig. 4-7
Dependence of travel on normalization and YA and YE as shown by an 80 mm linear actuator.
Tight closing with manipulated variable (see Fig. 4-6)
With this function the valve can be moved to its seat with maximum
actuating power (maintained contact of the piezovalves). The tight clo-
sing function can be activating on one side only or for both end posi-
tions. YCLS is activated when the setpoint is below 0.5 % or above
99.5% of the setpoint flow.
As the setpoint range refers to 0 – 100 % with YA and YE, the activa-
tion point of the tight closing function with reference to the flow can be
set lower with YA and higher with YE.
26.YCLS