Moniteur 50 Series SMART Positioners User Manual
Page 115
A-7
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Slot
Index
abs
Index
rel
Ele–
ment
Default Value
Object
Parameter Description
Data Type
Anzahl
cyclic
read
write
Device Management
1
0
1
HEADER
unsigned16
6
r
1
0x0000
Dir_ID
Directory ID (reserved)
2
0x0001
Num_Dir_Rev
Directory Revision Number
3
0x0001
Num_Dir_Obj
Number of Directory Objects (Directories)
4
0x0006
Num_Dir_Entries
Total Number of Directory Entries
5
0x0001
First_Comp_Dir_Entry
Entry number of first Composite List Dir Entry
6
0x0003
Num_Comp_Dir_Entry
Number of Composite List Directory Entries
1
1
2
COMPOSITE_LIST_DIRECTORY_E
NTRY
unsigned16
12
r
1
0x0104
Start_PB_Ref
Directory Index Physical Block (Resource
Block)
0x0001
Num_PB
Number of Physical Blocks (1)
2
0x0105
Start_First_TB_Ref
Directory Index for first Transducer Block
0x0001
Num_TB
Number of Transducer Blocks
3
0x0106
Start_First_FB_Ref
Directory Index for first Function Block
0x0001
Num_FB
Number of Function Blocks
4
0x010E
Slot_Index_PB
Communication related address index to PB
0x004c
Num_PB_Param
(Incl. reserved cells)
5
0x0197
Slot_Index_TB
(Absolute index)
0x0065
Num_TB_Param
(Incl. reserved cells)
6
0x015a
Slot_Index_FB
(Absolute index)
0x003d
Num_FB_Param
(Incl. reserved cells)
Physical Block
1
14
0
BLOCK_OBJECT
Block characteristic
ds32
1
r
1
250
Reserved
2
0x01
Block Object
Block type (physical)
3
0x02
Parent Class
4
250
Class
5
0x00000000
DD–Reference (reserved)
6
0
DD–Revision (reserved)
7
0x4002
Profile
PA profile number assigned by PNO
for PROFIBUS – PA = 64, Compact Class B
8
0x0300
Profile Revision
9
0x00
Execution Time
for future use
10
0x004c
Number of Parameters
11
0x004B
Index of VIEW 1
12
0x01
Number of View Lists
Standard Parameters
15
1
0
ST_REV
Counter that is incremented on every
change of configuration parameters
unsigned16
1
r
16
2
TAG_DESC
Unique tag in the system that
the user can specify
visible_string
32
r, w
17
3
0
STRATEGY
Strategy
unsigned16
1
r, w
18
4
0
ALERT_KEY
Value can be written to by user
for alarm processing
unsigned8
1
r, w
19
5
0x08
TARGET_MODE
Target mode of the PB = Auto
unsigned8
1
r, w
20
6
MODE_BLK
Set block mode
ds37
1
r
1
0x08
Actual
Auto
2
0x08
Permitted
Auto
3
0x08
Normal
Auto
21
7
ALARM_SUM
Alarm status
ds42
1
r
1
0x0000
Current_Alarm
2
0x0000
Unacknowledged
3
0x0000
Unreported