Technical Data

6-4

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

6DR4000–1N/–2N and
6DR4001–1N

6DR4000–1E/–2E and
6DR4001–1E

Current input i

w

Nominal signal range

0 or 4 to 20 mA

Load voltage at 20 mA

v

0.85 V without HART module

v

2.4 V with HART module

Static destruction limit

"

40 mA

Internal capacitance

C

i

19 nF

Internal inductance

L

i

0.22 mH

For connection to intrinsically
safe current sources
with

U

i

v

30 V

J

i

v

100 mA

P

i

v

1 W

Electrical isolation

between U

H

and J

w

between U

H

and J

w

(2 intrinsically safe circuits)

Test voltage 50 Hz 1 min

500 V

rms

Binary input BE1 (electrically
connected with J

w

circuit)

can be used for isolated contact

max. contact load

v

5

µ

A at 3 V