Operation

4-21

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

Safety position

This parameter is used to move the actuator into a set safety position if
communication fails.

Three settings are possible

FSVl

the actuator must continue to control with the parameterized safety set-
point

FSSP

the actuator must continue to control with the last effective setpoint

FSAC

Here this outlet air valve is opened and the single–action actuator
moves to its final position by spring power.

Monitoring time for setting the safety position

In the event of a failure of communication, the positioner moves to the
safety position after the set value has elapsed.

Safety setpoint

Specification for the safety position.

Station number

So that the devices on the bus can be addressed separately, a sepa-
rate station number must be set on each device.

46.FSTY

47.FSTI

48.FSVL

49.STNR