beautypg.com

A-11 – Moniteur 50 Series SMART Positioners User Manual

Page 119

background image

A-11

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

155

4

0

ALERT_KEY

Value can be written to by the user
for alarm processing

unsigned8

1

r, w

156

5

0x08

TARGET_MODE

Target mode of the PB = Auto

unsigned8

1

r, w

157

6

MODE_BLK

Set block mode

ds37

1

r

1

0x08

Actual

Auto

2

0x98

Permitted Auto, O/S, LO

Auto

3

0x08

Normal

Auto

158

7

ALARM_SUM

Alarm status

ds42

1

r

1

0x0000

Current_Alarm

2

0x0000

Unacknowledged

3

0x0000

Unreported

4

0x0000

Disabled

Parameter of the Transducer Block
(mandatory and optional)

160

9

0.0

ACT_STROKE_TIME_DEC

Calculated stroke time for OPENING

float

1

r

161

10

0.0

ACT_STROKE_TIME_INC

Calculated stroke time for CLOSING

float

1

r

168

17

1

TAB_ENTRY

Index

unsigned8

1

r, w

169

18

TAB_X_Y_VALUE

Tab position

float

2

r, w

1

X_Value

2

Y_Value

170

19

21

TAB_MIN_NUMBER

Min. possible tabs

unsigned8

1

r

171

20

21

TAB_MAX_NUMBER

Max. possible tabs

unsigned8

1

r

172

21

21

TAB_ACTUAL_NUMBER

Number of tabs currently stored

unsigned8

1

r

173

22

1

DEADBAND

Deadband of the controller

float

1

r, w

174

23

DEVICE_CALIB_DATE

Calibration date of the device

octet_string

8

r, w

175

24

DEVICE_CONFIG_DATE

Configuration date of the device

octet_string

8

r, w

176

25

0

LIN_TYPE

Linearization type

unsigned8

1

r, w

183

32

RATED_TRAVEL

Rated travel of the valve

ds33

1

r

1

0

Value

2

0

Status

184

33

0

SELF_CALIB_CMD

Calibration start

unsigned8

1

w

185

34

0

SELF_CALIB_STATUS

Status of calibration

unsigned8

1

r

189

38

0.0

SETP_CUTOFF_DEC

Tight closure if less than

float

1

r, w

190

39

100.0

SETP_CUTOFF_INC

Tight closure if greater than

float

1

r, w

196

45

0

TOTAL_VALVE_TRAVEL

Absolute travel integral

float

1

r, w

197

46

0

TOTAL_VALVE_TRAVEL_LIMIT

Limit value for the absolute travel integral

float

1

r, w

198

47

0

TRAVEL_LIMIT_LOW

Manipulated variable limitation

ds33

1

r, w

1

0

Value

2

0

Status

199

48

0

TRAVEL_LIMIT_UP

Manipulated variable limitation

ds33

1

r, w

1

100.0

Value

2

0

Status

200

49

0

TRAVEL_RATE_DEC

Required travel rate for OPENING

float

1

r, w

201

50

0

TRAVEL_RATE_INC

Required travel rate for CLOSING

float

1

r, w

202

51

VALVE_MAINT_DATE

Date of valve maintenance

octet_string

8

r, w

206

55

0

TAB_OP_CODE

Operation code

unsigned8

1

r, w

207

56

0

TAB_STATUS

unsigned8

1

x

208

57

POSITIONING_VALUE

Positioning value

ds33

1

r, w

1

0

Value

2

0x4f

Status