A-11 – Moniteur 50 Series SMART Positioners User Manual
Page 119
A-11
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
155
4
0
ALERT_KEY
Value can be written to by the user
for alarm processing
unsigned8
1
r, w
156
5
0x08
TARGET_MODE
Target mode of the PB = Auto
unsigned8
1
r, w
157
6
MODE_BLK
Set block mode
ds37
1
r
1
0x08
Actual
Auto
2
0x98
Permitted Auto, O/S, LO
Auto
3
0x08
Normal
Auto
158
7
ALARM_SUM
Alarm status
ds42
1
r
1
0x0000
Current_Alarm
2
0x0000
Unacknowledged
3
0x0000
Unreported
4
0x0000
Disabled
Parameter of the Transducer Block
(mandatory and optional)
160
9
0.0
ACT_STROKE_TIME_DEC
Calculated stroke time for OPENING
float
1
r
161
10
0.0
ACT_STROKE_TIME_INC
Calculated stroke time for CLOSING
float
1
r
168
17
1
TAB_ENTRY
Index
unsigned8
1
r, w
169
18
TAB_X_Y_VALUE
Tab position
float
2
r, w
1
X_Value
2
Y_Value
170
19
21
TAB_MIN_NUMBER
Min. possible tabs
unsigned8
1
r
171
20
21
TAB_MAX_NUMBER
Max. possible tabs
unsigned8
1
r
172
21
21
TAB_ACTUAL_NUMBER
Number of tabs currently stored
unsigned8
1
r
173
22
1
DEADBAND
Deadband of the controller
float
1
r, w
174
23
DEVICE_CALIB_DATE
Calibration date of the device
octet_string
8
r, w
175
24
DEVICE_CONFIG_DATE
Configuration date of the device
octet_string
8
r, w
176
25
0
LIN_TYPE
Linearization type
unsigned8
1
r, w
183
32
RATED_TRAVEL
Rated travel of the valve
ds33
1
r
1
0
Value
2
0
Status
184
33
0
SELF_CALIB_CMD
Calibration start
unsigned8
1
w
185
34
0
SELF_CALIB_STATUS
Status of calibration
unsigned8
1
r
189
38
0.0
SETP_CUTOFF_DEC
Tight closure if less than
float
1
r, w
190
39
100.0
SETP_CUTOFF_INC
Tight closure if greater than
float
1
r, w
196
45
0
TOTAL_VALVE_TRAVEL
Absolute travel integral
float
1
r, w
197
46
0
TOTAL_VALVE_TRAVEL_LIMIT
Limit value for the absolute travel integral
float
1
r, w
198
47
0
TRAVEL_LIMIT_LOW
Manipulated variable limitation
ds33
1
r, w
1
0
Value
2
0
Status
199
48
0
TRAVEL_LIMIT_UP
Manipulated variable limitation
ds33
1
r, w
1
100.0
Value
2
0
Status
200
49
0
TRAVEL_RATE_DEC
Required travel rate for OPENING
float
1
r, w
201
50
0
TRAVEL_RATE_INC
Required travel rate for CLOSING
float
1
r, w
202
51
VALVE_MAINT_DATE
Date of valve maintenance
octet_string
8
r, w
206
55
0
TAB_OP_CODE
Operation code
unsigned8
1
r, w
207
56
0
TAB_STATUS
unsigned8
1
x
208
57
POSITIONING_VALUE
Positioning value
ds33
1
r, w
1
0
Value
2
0x4f
Status