Moniteur 50 Series SMART Positioners User Manual
Page 103
Technical Data
6-5
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Electrical data: basic instrument with PROFIBUS PA
6DR4100–1N
6DR4100–2N
6DR4101–1N
6DR4100–1E
6DR4100–2E
6DR4101–1E
Degree of protection acc. to
EN 50014 and EN 50020
EEx ia IIC T4/T5/T6
Ambient temperature
T4 –30 to +80
°
C
T5 –30 to +65
°
C
T6 –30 to +50
°
C
Place of installation
zone 1
Power supply
conducted on bus
Bus voltage
9 to 32 V
9 to 24 V
Power consumption
12 mA
"
10 %
Electronic
current limitation
I
max
=
v
16 mA in case of fault
Effective internal inductance
L
i
v
7.2 mH
Effective internal capacitance
C
i
v
550 pF
Connection
certified intrinsically safe
circuit
Power supply unit
U
S
= 24 V; J
S
= 128 mA
Electrical isolation
Between BUS and secondary
circuit
Between BUS and secondary
circuit
(2 intrinsically safe circuits)
Test voltage 50 Hz 1 min
500 V
rms
Binary input BE1 (electrically
connected with secondary cir-
cuit)
can be used for isolated contact
max. contact load
v
5
µ
A at 3 V
Communication function
Layer 1+2 acc. to PROFIBUS PA, transmission technology
acc. to IEC 1158–2; slave
Layer 7 (protocol layer) acc. to PROFIBUS DP, standard EN
50 170 with the extended PROFIBUS func tionality (all data
non–cyclic, value of manipulated variable, feedback signals
and status also cyclic)
C2_Connections after com-
munication interruption.
4 connections with master class 2 are supported, automatic
connection breakdown 60 s
Device profile
PROFIBUS PA profile B, version 3.0; more than 150 objects
Response time to master
telegram
Typ. 10 ms
Device address
126 (in the as–supplied state)
PC parameterization software
SIMATIC PDM executable on Windows 95 or Windows NT;
supports all device objects
The software is not contained in the scope of supply.