beautypg.com

Moniteur 50 Series SMART Positioners User Manual

Page 103

background image

Technical Data

6-5

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

Electrical data: basic instrument with PROFIBUS PA

6DR4100–1N
6DR4100–2N
6DR4101–1N

6DR4100–1E
6DR4100–2E
6DR4101–1E

Degree of protection acc. to
EN 50014 and EN 50020

EEx ia IIC T4/T5/T6

Ambient temperature

T4 –30 to +80

°

C

T5 –30 to +65

°

C

T6 –30 to +50

°

C

Place of installation

zone 1

Power supply

conducted on bus

Bus voltage

9 to 32 V

9 to 24 V

Power consumption

12 mA

"

10 %

Electronic
current limitation

I

max

=

v

16 mA in case of fault

Effective internal inductance

L

i

v

7.2 mH

Effective internal capacitance

C

i

v

550 pF

Connection

certified intrinsically safe
circuit

Power supply unit

U

S

= 24 V; J

S

= 128 mA

Electrical isolation

Between BUS and secondary
circuit

Between BUS and secondary
circuit

(2 intrinsically safe circuits)

Test voltage 50 Hz 1 min

500 V

rms

Binary input BE1 (electrically
connected with secondary cir-
cuit)

can be used for isolated contact

max. contact load

v

5

µ

A at 3 V

Communication function

Layer 1+2 acc. to PROFIBUS PA, transmission technology
acc. to IEC 1158–2; slave

Layer 7 (protocol layer) acc. to PROFIBUS DP, standard EN
50 170 with the extended PROFIBUS func tionality (all data
non–cyclic, value of manipulated variable, feedback signals
and status also cyclic)

C2_Connections after com-
munication interruption.

4 connections with master class 2 are supported, automatic
connection breakdown 60 s

Device profile

PROFIBUS PA profile B, version 3.0; more than 150 objects

Response time to master
telegram

Typ. 10 ms

Device address

126 (in the as–supplied state)

PC parameterization software

SIMATIC PDM executable on Windows 95 or Windows NT;

supports all device objects

The software is not contained in the scope of supply.