Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

Response threshold of alarm 1

and

Response threshold of alarm 2

The response thresholds refer to the mechanical path (MPOS scale).

Function of alarm output on fault

The fault alarm for monitoring the system deviation over time can also
be triggered by the following events:

Loss of power

Process fault

Actuator fault

Valve fault

Loss of pressure

The alarm fault can also be logically ORed with the non–automatic si-
gnal (Manual or Configuring) and the binary inputs.

The direction of action of the binary outputs can be adapted from high
active to low active subsequent systems.

Monitoring time for setting of alarms

The set value (s) defines the time within which the positioner must have
reached the corrected state. The corresponding response threshhold is
defined with parameter 35.

The alarm output is set if the set time is exceeded.

Response threshold of alarm

A value (%) for the permitted system deviation for the purposes of trig-
gering the alarm can be set here.

If parameters 34 and 35 are both set to “Auto” the alarm is set if the
short–step zone is not reached within a certain time. This time is 5x the
initialization time within 5 to 95 % of the travel and 10x the initialization
time outside 10 to 90%.

Preset

Restoration of the factory setting and initialization reset

Note

After “Preset” the positioner must be re-initialized. All the maintenance
parameters calculated so far are reset.

31.A1

32.A2

33. FCT

34. TIM

35. LIM

36.PRST