beautypg.com

Moniteur 50 Series SMART Positioners User Manual

Page 34

background image

Design and Method of Operation

2-16

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

2.5.1 HART module (devices without PROFIBUS PA only)

The HART interface is used for communication between the instrument
and a HART communicator or a PC or notebook.

The HART interface permits the following functions:

Remote process operation and monitoring with the option of speci-
fied value setting

Reading and writing the configuration data

Reading the maintenance parameters

With the communication software SIPROM PS2, which can be ordered
separately (Order No. see Supply Range Section 7), and the HART
modem, which can also be ordered separately, it is also possible to
store the data in a file and compare old and new values.

This software was developed on the basis of the GMA user interface
and runs under “MS-WINDOWS” in a largely self-explanatory way.

Communication with the HART instrument is indicated in the bottom
line of the display by “HRT”.

Note

Operation of the positioner has priority over input via the HART inter-
face.

Communication is broken off if the auxiliary power to the positioner
fails.

The HART module (2) is plugged onto the post connectors on the mo-
therboard to the left of the display (see Fig. 2-12). Before you do this
you must first remove the plug-in jumper (7) on the motherboard. When
plugging-in the module make sure the connector coding is correct.

The HART communicator or HART modem must be connected to the
positioner as shown in Fig. 2-14.

Function

Installation