Preparing for Operation
3-14
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
3. Insert the prepared bus cable through the cable gland.
4. Fix the shield to the housing with the clip and the two screws.
5. Screw the cable gland tight.
6. Connect the red and green conductors as shown in Fig. 3-12 to ter-
minals 3 and 7 of the basic PCB. (The polarity is irrelevant.)
5
80
10
Bus cable 6XV1 830–5AH10
or 6XV1 830–5BH10
Cable shield
Fig. 3-11
Preparation of the bus cable, devices with PROFIBUS PA
9
3
7
10
Bus cable
Cable gland
Basic PCB
Cable clip
Housing
Blanking cover
Module cover
Cable
screen
Fig. 3-12
Connection of the bus cable, devices with PROFIBUS PA
For fault–free communication the bus must be fitted with terminating
resistors at both ends. At the end near to the control system, termina-
tion is ensured by the bus terminator already in the coupler or link. At
the remote end of the bus, termination must be ensured by an addi-
tional terminator.
!
Warning
In intrinsically safe circuits, only approved bus terminators, splitters,
cables etc. must be used.