Preparing for Operation

3-14

Positioner SIPART PS2/SIPART PS2 PA

C79000-G7476-C150–01

3. Insert the prepared bus cable through the cable gland.

4. Fix the shield to the housing with the clip and the two screws.

5. Screw the cable gland tight.

6. Connect the red and green conductors as shown in Fig. 3-12 to ter-

minals 3 and 7 of the basic PCB. (The polarity is irrelevant.)

5

80

10

Bus cable 6XV1 830–5AH10

or 6XV1 830–5BH10

Cable shield

Fig. 3-11

Preparation of the bus cable, devices with PROFIBUS PA

9

3
7

10

Bus cable

Cable gland

Basic PCB

Cable clip

Housing

Blanking cover

Module cover

Cable
screen

Fig. 3-12

Connection of the bus cable, devices with PROFIBUS PA

For fault–free communication the bus must be fitted with terminating
resistors at both ends. At the end near to the control system, termina-
tion is ensured by the bus terminator already in the coupler or link. At
the remote end of the bus, termination must be ensured by an addi-
tional terminator.

!

Warning

In intrinsically safe circuits, only approved bus terminators, splitters,
cables etc. must be used.