Operation

4-25

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

The discrete position of the valve is displayed as a value (1 byte) with
the following meaning:

0 = not initialized

1 = valve closed

2 = valve open

3 = valve in intermediate state

There is a status for this value too (1 byte)

The checkback is displayed bit–coded in 3 bytes:

Byte

Bit

Meaning for ”1”

0

0

Device in failsafe position

1

Request for local operation

2

Device is operated locally

3

Emergency operation active

4

Deviation of the motion direction

5

Stop reached (valve not completely open)

6

Stop reached (valve not completely closed)

7

Operating timeout

1

0

Valve is opened

1

Valve is closed

2

Parameters have been changed

3

Simulation operation

4

Fault

5

Fault in the control

6

Control inactive

7

Self–test active

2

0

Path integral exceeded

1

Additional input active

2

3

4

5

6

7

In remote cascade mode (actual mode = remote cascade), the remote
cascade input is used as the setpoint. Remote cascade input consists
of a floating–point value (4 bytes) and status (1 bytes)

Position discrete

Checkback

Remote cascade
input